B-48 C70 Capacitor Bank Protection and Control System GE MultilinB.4 MEMORY MAPPING APPENDIX BB9E52 Voltage differential 1 stage 1C pickup 0.001 to 1.000 pu 0.001 F001 109E53 Voltage differential 1 stage 2C pickup 0.001 to 1.000 pu 0.001 F001 209E54 Voltage differential 1 stage 3C pickup 0.001 to 1.000 pu 0.001 F001 309E55 Voltage differential 1 stage 4C pickup 0.001 to 1.000 pu 0.001 F001 409E56 Voltage differential 1 stage 1 pickup delay 0 to 600.00 s 0.01 F001 30009E57 Voltage differential 1 stage 2 pickup delay 0 to 600.00 s 0.01 F001 10009E58 Voltage differential 1 stage 3 pickup delay 0 to 600.00 s 0.01 F001 1009E59 Voltage differential 1 stage 4 pickup delay 0 to 600.00 s 0.01 F001 209E5A Voltage differential 1 dropout delay 0 to 600.00 s 0.01 F001 259E5B Voltage differential 1 stage 1 block 0 to 4294967295 --- 1 F300 09E5D Voltage differential 1 stage 2 block 0 to 4294967295 --- 1 F300 09E5F Voltage differential 1 stage 3 block 0 to 4294967295 --- 1 F300 09E61 Voltage differential 1 stage 4 block 0 to 4294967295 --- 1 F300 09E63 Voltage differential 1 target 0 to 2 --- 1 F109 0 (Self-Reset)9E64 Voltage differential 1 events 0 to 1 --- 1 F102 0 (Disabled)9E65 ...Repeated for voltage differential 29E8A ...Repeated for voltage differential 3VT Fuse Failure (Read/Write Setting) (6 modules)A09A VT Fuse Failure Function 0 to 1 --- 1 F102 0 (Disabled)A09B VT Fuse Failure Neutral Wire Open Function 0 to 1 --- 1 F102 0 (Disabled)A09C VT Fuse Failure Neutral Wire Open 3rd Harmonic Pickup 0 to 3 pu 0.001 F001 100A09D ...Repeated for module number 2A0A0 ...Repeated for module number 3A0A3 ...Repeated for module number 4A0A6 ...Repeated for module number 5A0A9 ...Repeated for module number 6A0AC VTFF x V0 3rd harmonic 0 to 999999.999 V 0.001 F060 0Selector switch actual values (read only)A210 Selector switch 1 position 1 to 7 --- 1 F001 0A211 Selector switch 2 position 1 to 7 --- 1 F001 1Selector switch settings (read/write, 2 modules)A280 Selector 1 Function 0 to 1 --- 1 F102 0 (Disabled)A281 Selector 1 Range 1 to 7 --- 1 F001 7A282 Selector 1 Timeout 3 to 60 s 0.1 F001 50A283 Selector 1 Step Up 0 to 4294967295 --- 1 F300 0A285 Selector 1 Step Mode 0 to 1 --- 1 F083 0 (Time-out)A286 Selector 1 Acknowledge 0 to 4294967295 --- 1 F300 0A288 Selector 1 Bit0 0 to 4294967295 --- 1 F300 0A28A Selector 1 Bit1 0 to 4294967295 --- 1 F300 0A28C Selector 1 Bit2 0 to 4294967295 --- 1 F300 0A28E Selector 1 Bit Mode 0 to 1 --- 1 F083 0 (Time-out)A28F Selector 1 Bit Acknowledge 0 to 4294967295 --- 1 F300 0A291 Selector 1 Power Up Mode 0 to 2 --- 1 F084 0 (Restore)A292 Selector 1 Target 0 to 2 --- 1 F109 0 (Self-reset)A293 Selector 1 Events 0 to 1 --- 1 F102 0 (Disabled)A294 Reserved (10 items) --- --- 1 F001 0A29E ...Repeated for Selector 2Digital Counter (Read/Write Setting) (8 modules)A300 Digital Counter 1 Function 0 to 1 --- 1 F102 0 (Disabled)A301 Digital Counter 1 Name --- --- --- F205 “Counter 1"A307 Digital Counter 1 Units --- --- --- F206 (none)A30A Digital Counter 1 Block 0 to 4294967295 --- 1 F300 0A30C Digital Counter 1 Up 0 to 4294967295 --- 1 F300 0A30E Digital Counter 1 Down 0 to 4294967295 --- 1 F300 0Table B–9: MODBUS MEMORY MAP (Sheet 41 of 61)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT