GE Multilin L90 Line Current Differential System 5-155 SETTINGS 5.2 PRODUCT SETUP5• SESSION LOCKOUT: This setting specifies the number of failed authentications (the default is three and the maxi-mum is 99) before the device blocks subsequent authentication attempts for the lockout period. A value of zero meanslockout is disabled.• SESSION LOCKOUT PERIOD: This setting specifies the period of time in minutes of a lockout period (the default isthree and the maximum is 9999). A value of 0 means that there is no lockout period.e) RESTORE DEFAULTSPATH: SETTINGS PRODUCT SETUP SECURITY RESTORE DEFAULTS• LOAD FACTORY DEFAULTS: This setting is used to reset all the settings, communication and security passwords. AnAdministrator role is used to change this setting and a Supervisor role (if not disabled) approves it.f) SUPERVISORYPATH: SETTINGS PRODUCT SETUP SECURITY SUPERVISORY RESTORE DEFAULTSLOAD FACTORYDEFAULTS: NoRange: Yes, No SUPERVISORYLOCALAUTHENTICATION:YesRange: Yes, NoMESSAGE Bypass Access:DisableRange: Enable, DisableMESSAGE LOCK RELAY:DisableRange: Enable, DisableMESSAGE FACTORY SERVICE:MODE: DisableRange: Enable, DisableMESSAGE SELF TESTS See belowMESSAGE SUPERVISOR ROLE:DisableRange: Enable, DisableMESSAGE SERIAL INACTIVITYTIMEOUT: 3Range: 1 to 9999 minutes