5-236 L90 Line Current Differential System GE Multilin5.7 CONTROL ELEMENTS 5 SETTINGS5Figure 5–128: EXAMPLE FLEXLOGIC CONTROL OF A SETTINGS GROUP5.7.4 SELECTOR SWITCHPATH: SETTINGS CONTROL ELEMENTS SELECTOR SWITCH SELECTOR SWITCH 1(2) SELECTOR SWITCH 1SELECTOR 1 FUNCTION:DisabledRange: Disabled, EnabledMESSAGE SELECTOR 1 FULLRANGE: 7Range: 1 to 7 in steps of 1MESSAGE SELECTOR 1 TIME-OUT:5.0 sRange: 3.0 to 60.0 s in steps of 0.1MESSAGE SELECTOR 1 STEP-UP:OffRange: FlexLogic operandMESSAGE SELECTOR 1 STEP-UPMODE: Time-outRange: Time-out, AcknowledgeMESSAGE SELECTOR 1 ACK:OffRange: FlexLogic operandMESSAGE SELECTOR 1 3BIT A0:OffRange: FlexLogic operandMESSAGE SELECTOR 1 3BIT A1:OffRange: FlexLogic operandMESSAGE SELECTOR 1 3BIT A2:OffRange: FlexLogic operandMESSAGE SELECTOR 1 3BITMODE: Time-outRange: Time-out, AcknowledgeMESSAGE SELECTOR 1 3BIT ACK:OffRange: FlexLogic operandMESSAGE SELECTOR 1 POWER-UPMODE: RestoreRange: Restore, Synchronize, Sync/RestoreMESSAGE SELECTOR 1 TARGETS:Self-resetRange: Self-reset, Latched, DisabledMESSAGE SELECTOR 1 EVENTS:DisabledRange: Disabled, Enabled101 VIRT IP 1 ON (VI1)2 CONT IP 1 ON (H5A)3OR (2)OR (2)4 PHASE TOC1 PKP5 NOT6 PHASE TOC2 PKP7 NOT8AND (3)AND (3)9= VIRT OP 1 (VO1)= VIRT OP 1 (VO1)END 842789A1.CDR