GE Multilin L90 Line Current Differential System B-79APPENDIX B B.4 MEMORY MAPPINGBEC09 Synchrocheck 1 Dead V2 Maximum Voltage 0 to 1.25 pu 0.01 F001 30EC0A Synchrocheck 1 Live V1 Minimum Voltage 0 to 1.25 pu 0.01 F001 70EC0B Synchrocheck 1 Live V2 Minimum Voltage 0 to 1.25 pu 0.01 F001 70EC0C Synchrocheck 1 Target 0 to 2 --- 1 F109 0 (Self-reset)EC0D Synchrocheck 1 Events 0 to 1 --- 1 F102 0 (Disabled)EC0E Synchrocheck 1 Block 0 to 4294967295 --- 1 F300 0EC10 Synchrocheck 1 Frequency Hysteresis 0 to 0.1 Hz 0.01 F001 6EC11 ...Repeated for Synchrocheck 2EC22 ...Repeated for Synchrocheck 3EC33 ...Repeated for Synchrocheck 4Phasor Measurement Unit Frequency Trigger (Read/Write Setting) (4 modules)ECCC PMU 1 Frequency Trigger Function 0 to 1 --- 1 F102 0 (Disabled)ECCD PMU 1 Frequency Trigger Low Frequency 20 to 70 Hz 0.01 F001 4900ECCE PMU 1 Frequency Trigger High Frequency 20 to 70 Hz 0.01 F001 6100ECCF PMU 1 Frequency Trigger Pickup Time 0 to 600 s 0.01 F001 10ECD0 PMU 1 Frequency Trigger Dropout Time 0 to 600 s 0.01 F001 100ECD1 PMU 1 Frequency Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0ECD7 PMU 1 Frequency Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)ECD8 PMU 1 Frequency Trigger Events 0 to 1 --- 1 F102 0 (Disabled)Setting file template values (read only)ED00 FlexLogic displays active 0 to 1 --- 1 F102 1 (Enabled)ED01 Undefined --- --- --- F205 (none)ED07 Last settings change date 0 to 4294967295 --- 1 F050 0ED09 Template bitmask (750 items) 0 to 65535 --- 1 F001 0Phasor Measurement Unit Records (Read Only)EFFF PMU Recording Number of Triggers 0 to 65535 samples 1 F001 0Table B–9: MODBUS MEMORY MAP (Sheet 71 of 71)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT