5-130 L90 Line Current Differential System GE Multilin5.5 FLEXLOGIC 5 SETTINGS5FIXED OPERANDS Off Logic = 0. Does nothing and may be used as a delimiter in an equation list;used as ‘Disable’ by other features.On Logic = 1. Can be used as a test setting.INPUTS/OUTPUTS:Contact inputsCont Ip 1 OnCont Ip 2 OnCont Ip 1 OffCont Ip 2 Off(will not appear unless ordered)(will not appear unless ordered)(will not appear unless ordered)(will not appear unless ordered)INPUTS/OUTPUTS:Contact outputs,current(from detector onform-A output only)Cont Op 1 IOnCont Op 2 IOn(will not appear unless ordered)(will not appear unless ordered)INPUTS/OUTPUTS:Contact outputs,voltage(from detector onform-A output only)Cont Op 1 VOnCont Op 2 VOn(will not appear unless ordered)(will not appear unless ordered)Cont Op 1 VOffCont Op 2 VOff(will not appear unless ordered)(will not appear unless ordered)INPUTS/OUTPUTS:Direct inputDirect I/P 1-1 OnDirect I/P 1-8 On(appears only when an inter-relay communications card is used)(appears only when inter-relay communications card is used)Direct I/P 2-1 OnDirect I/P 2-8 On(appears only when inter-relay communications card is used)(appears only when inter-relay communications card is used)INPUTS/OUTPUTS:Remote double-point status inputsRemDPS Ip 1 BADRemDPS Ip 1 INTERMRemDPS Ip 1 OFFRemDPS Ip 1 ONAsserted while the remote double-point status input is in the bad state.Asserted while the remote double-point status input is in the intermediatestate.Asserted while the remote double-point status input is off.Asserted while the remote double-point status input is on.REMDPS Ip 2... Same set of operands as per REMDPS 1 aboveINPUTS/OUTPUTS:Remote inputsREMOTE INPUT 1 OnREMOTE INPUT 2 OnREMOTE INPUT 2 OnREMOTE INPUT 32 OnFlag is set, logic=1Flag is set, logic=1Flag is set, logic=1Flag is set, logic=1INPUTS/OUTPUTS:Virtual inputsVirt Ip 1 OnVirt Ip 2 OnVirt Ip 3 OnVirt Ip 64 OnFlag is set, logic=1Flag is set, logic=1Flag is set, logic=1Flag is set, logic=1INPUTS/OUTPUTS:Virtual outputsVirt Op 1 OnVirt Op 2 OnVirt Op 3 OnVirt Op 96 OnFlag is set, logic=1Flag is set, logic=1Flag is set, logic=1Flag is set, logic=1LED INDICATORS:Fixed front panelLEDsLED IN SERVICELED TROUBLELED TEST MODELED TRIPLED ALARMLED PICKUPLED VOLTAGELED CURRENTLED FREQUENCYLED OTHERLED PHASE ALED PHASE BLED PHASE CLED NEUTRAL/GROUNDAsserted when the front panel IN SERVICE LED is on.Asserted when the front panel TROUBLE LED is on.Asserted when the front panel TEST MODE LED is on.Asserted when the front panel TRIP LED is on.Asserted when the front panel ALARM LED is on.Asserted when the front panel PICKUP LED is on.Asserted when the front panel VOLTAGE LED is on.Asserted when the front panel CURRENT LED is on.Asserted when the front panel FREQUENCY LED is on.Asserted when the front panel OTHER LED is on.Asserted when the front panel PHASE A LED is on.Asserted when the front panel PHASE B LED is on.Asserted when the front panel PHASE C LED is on.Asserted when the front panel NEUTRAL/GROUND LED is on.LED INDICATORS:LED testLED TEST IN PROGRESS An LED test has been initiated and has not finished.LED INDICATORS:User-programmableLEDsLED USER 1 Asserted when user-programmable LED 1 is on.LED USER 2 to 48 The operand above is available for user-programmable LEDs 2 through 48.Table 5–10: L90 FLEXLOGIC OPERANDS (Sheet 9 of 10)OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION