GE Multilin L90 Line Current Differential System 5-2715 SETTINGS 5.7 CONTROL ELEMENTS5The continuous monitor logic is intended to detect the operation of any tripping element that has operated under normalload conditions; that is, when the disturbance detector has not operated. Because all tripping is supervised by the distur-bance detector function, no trip will be issued under these conditions. This could occur when an element is incorrectly setso that it may misoperate under load. The continuous monitor can detect this state and issue an alarm and/or block the trip-ping of the relay.Figure 5–148: CONTINUOUS MONITOR SCHEME LOGICSETTINGCONT MONITORFUNCTION:Disabled = 0Enabled = 1SETTINGCONSTANTCONTMONITORTIMERt pkp = 1 sect RST = 0CONT MONITORI_SUPV:Off = 0SETTINGCONT MONITORI_OP:Off = 0SETTINGCONT MONITORV_SUPV:Off = 0SETTINGCONT MONITORV_OP:Off = 0 ANDORANDANDAND827049A3.vsdFLEXLOGIC OPERANDSCONT MONITOR PKPCONT MONITOR DPOCONT MONITOR OP