V00786ONOFFStartInhibitionTime Between Start (default value)Inhibit Start Time (default value)ONOFFMotor startP0656ENbFigure 81: Time between starts15.2 NUMBER OF STARTS LIMITATIONRepeated starting, or intermittent operation of a motor, can generate dangerously high temperatures within themotor, unless sufficient time is allowed for cooling between starts.The P24xM relay incorporates several starts limitation facilities. This limitation is fully programmable.Restarting the motor from a hot thermal stateFor certain applications do not allow the motor time to cool down to a specified thermal state before a re-start ispermitted. The P24xM relay incorporates several features which allow a subsequent start from a hot thermal state.These are discussed in the section on 'thermal overload protection'.The motor accumulated run time displayed in the menu cell Motor Run. Time of the MEASUREMENTS 3 menu isinitiated each time the switching device is closed and remains closed.P24xM Chapter 6 - Current Protection FunctionsP24xM-TM-EN-2.1 161