204.17 Setting 934 – Latching Override cancelled by code useAllowed Values = 0 - 3 Default value = 0This setting is used to determine if the Latching Override function can becancelled by use of a code or whether the advanced code function isrequired.0 = Latching Override must be cancelled by advanced code function.1 = All users can cancel Latching Override.2 = Primary & Manager users can cancel Latching Override.3 = Only Manager users can cancel Latching Override.If this setting is not 0 and the Lock (or Auxiliary Lock) is latched on, thenthe use of a user code enabled for this feature will unlatch the relay andstart the normal timing for the output.4.18 Setting 935 – Lockout Standard Users via AdvancedCode FunctionAllowed Values = 0, 2 - 3 Default value = 0Enabling this function allows primary or manager users to use theadvanced code functions to lockout Standard Users (refer to page 12).0 = Function disabled.2 = Primary & Manager users can lockout Standard Users.3 = Manager users can lockout Standard Users.NOTE if this function is enabled (set to 2 or 3) Standard Users arealways locked out on power up.4.19 Setting 961 – Code LengthAllowed Values = 0, 3 - 8 Default value = 0Sets the length (number of digits) to use for the user codes and installercode.0 = Variable code length from 3 to 8 digits.3 - 8 = Number of digits for each code.NOTE programming this setting will erase all existing codes. The newvalue for this setting needs to be confirmed by entering the currentinstaller code then after the programming sequence, as shown below. 961