8 AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015Main Menu and Event Counts Screen The Main Menu2.1.2 Disable/EnablePressing the DISABLE/ENABLE soft key on the Main Menu brings up the point select screen fordisabling a device. From this screen, the user can disable a device installed on the system.Disable/Enable Point Selection.Figure 2.3 Point Select for Disable/Enable ScreenSoft KeysPOINT SELECT: Press this soft key to identify the type of point to disable/enable: the choicesthat will appear in parentheses next to the point format are DETECTOR, MODULE, VESDA, BELLCKT, ZONE, LOGIC ZONE, DAL SPEAKER CKT, or DAL ALL CKTS. Enter the address of thepoint using the keyboard. If there is an event in the display area, that address will be the default. Ifno event is present, the default format will be that of a detector.Disable/EnableA point can be disabled or enabled using this screen. Once a point has been selected, press theACCEPT soft key display the following.Figure 2.4 Disable/Enable ScreenD I S A B L E P O I N T S E L E C TP O I N T S E L E C T :N 1 0 4 L y y D z z z D E T E C T O R )N E X T S E L E C T I O N A C C E P TP R E V I O U S S E L E C T I O N B A C KD I S A B L E / E N A B L EA U T O M A T I C I N A C T I V EE L E V A T O R L O B B Y E A S T W I N GF I F T H F L O O R Z 0 0 5 S M O K E ( P H O T O )V A L U E S : 0 1 1 % O F A L A R M , 0 4 5 % O F P R E A L A R MD I S A B L E B A C K