AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 65Point Program PrealarmProgramSoft KeysLOGIC FUNCTION: Press to scroll through the list of possible logic functions.ACCEPT: Press to insert the logic function into the equation where the cursor is blinking, and toreturn to the previous screen.Add Time/DateThis screen appears when the ADD TIME/DATE soft key is pressed at the Logic ZoneProgramming Menu screenFigure 3.52 Add Time/Date to Logic Zone ScreenSoft KeysENTER TIME: _ _:_ _:_ _ Press this soft key to toggle between the time/date formats. Choose onebased on the type of time-based function used.3.4.5 Fault ZoneFault Zone ProgrammingFault zones provide a means of using a system fault input to effect an output. For instance, anannunciator fault can be used to activate an output device.The fault zone format is ZTxxx, where xxx is a number from one through one hundred. When afault zone format is entered at the Point Select screen, the same programming screens and choicesappear as for logic zones, except the zone format is a fault zone format. (Refer to paragraphs“Logic Zone Programming” on page 62 and the paragraphs following “Add Time/Date”).Refer to Appendix D, “CBE: Zones and Equations” for information on how to create a faultequation, and how they operate.Time-basedfunctionScreen Field Time/date formatDEL, SDEL, TIM ENTER TIME:_ _:_ _:_ _ HH:MM:SS, entered as military time (22:30:00 = 10:30 P.M.)TIM ENTER DATE:_ _-_ _-_ _ (MM-DD-YY)TIM ENTER DAY: MO (Use the TOGGLE DAY soft key that appears to scroll throughand choose a day of the week.L O G I C Z O N E P R O G R A M M I N G M E N UL O G I C Z O N E Z L x x x xA U T O M A T I C O F FD E LO V E R W R I T EE N T E R T I M E : 2 2 : 3 0 : 0 0 A C C E P TB A C K