136 AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015Smoke Control Station Programming Basic Programming: ConfigurationsH.6 Basic Programming: ConfigurationsThere are 16 possible smoke control system configurations. Refer to the following for possible con-figurations and the programming needed for each.Configuration 1 Parameters:Smoke Control: Non-LatchingFan Control and Status: 2 fan control modules, using CBE to start the fan and a module to monitor status of the fanFan Automation: When fan is in automation, the fan is off. When activated by the CBE, the fan turns on.Activating the fan start module will turn on the fan. Activating the fan stop module will turn off the fan. The fan status module willactivate then the fan is on and deactivate when the fan is off.A system reset will turn the fan off.Duct Detector: Not usedSCS: FSCS Switch Group Type 8 (CONon, CONoff, VERon)Configuration 1 Programming:System ProgrammingLatching FireMode:NoUse SingleStart/Stop:NoAction on CBE: StartPoint ProgrammingSmoke Detector: First CBE Zone programmed as Z001Duct Detector: N/AFan Start Point: L01M001Fan Stop Point: L01M002Fan Status Point: L01M003General and Logic Zone Programming:Fan CBE Zone: Z001, with Non-resettable Control, Silenceable, and Precedence Participation set to NODuct DetectorZone:N/AZLduct Zone: N/AZLstart Zone: N/AZLstop Zone: ZL302 programmed with the equation NOT(ZL301)SCS Dip Switch Settings:Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Switch 6Off On On On Off OnSCS Point Programming:ACS Point 1 ACS Point 2 ACS Point 3Mode: Control Mode: Control Mode: MonitorSource: L01M001 Source: L01M002 Source: L01M003Point Type: Fan Start Point Type: Fan Stop Point Type Fan StatusCBE Zone: Z001 CBE Zone: ZL302 CBE Zone: N/A