AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015 23Panel Program PrealarmProgram3.2.4 Panel SettingsPress the Panel Settings soft key on the Panel Program Menu 1 screen to choose panel settings.Figure 3.6 Panel Settings (1) ScreenSoft KeysLOCAL CONTROL: Press this soft key to toggle between YES and NO. This option disables (NO) orenables (YES) local panel control of the Signal Silence, System Reset, and Drill Fixed Function keys, aswell as SIGNAL SILENCE, SYSTEM RESET, and ACKNOWLEDGE soft keys. A setting of NO (disable)turns the panel piezo sounder off, overriding the next field if PIEZO is set to ON. Default: YESPIEZO: Press this soft key to toggle between OFF and ON. This option enables (ON) or disables(OFF) the panel piezo from sounding when alarms or faults occur. A setting of ON is overridden ifLOCAL CONTROL is set to NO. Default: ONDISPLAY ADDRESS: Press this soft key to toggle between YES and NO. Choose YES to displayall point address information at the top of event screens and in printouts. Choose NO to suppressaddress information display and printing. Default: YESREMINDER MENU: Press this soft key to bring up the Reminder Menu screen.ACCEPT: Press this soft key to save the information entered on this screen.MORE: Press this key to progress to the second Panel Settings screen.P A N E L S E T T I N G SL O C A L C O N T R O L : Y E S R E M I N D E R M E N UP I E Z O : O N M O R EA C C E P TD I S P L A Y A D D R E S S : Y E S B A C KNOTE: A setting of NO (disable) will disable key switch operation.NOTE: ACS devices programmed for acknowledge, signal silence, and system reset are not affected bythis setting: these commands will still function at the devices if LOCAL CONTROL is set to NO.