134 AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015Smoke Control Station Programming Basic Programming: Smoke Control DefaultsH.3 Basic Programming: Smoke Control DefaultsProgramming an annunciator as a smoke control device will automatically program the followingsettings. These settings can be modified via VeriFire Tools using the Smoke Control Wizard. Referto the VeriFire Tools help file for additional information.FAN NAME: Each fan will have a user programmable label (up to 20 characters). The Defaultlabel will match the Annunciator Board Label that can be programmed via Point Programming(refer to Section 3.4.6 on page 66).FAN START POINT: Address of the relay module associated with starting the fan for the SCSannunciator.FAN STOP POINT: Address of the relay module associated with stopping the fan for the SCSannunciator.FAN STATUS: Address of the monitor module used to monitor whether the fan is on or off.DUCT DETECTOR ZONE (ZLduct): General zone of the duct detector(s) which monitor theair quality for the fan. If using a Tracking Non-fire type duct detector, use the duct detector zone(CBE position 1 of the associated duct detector) for this setting. If using a duct detector zone, thena logic zone will be defined to track the activation of the duct detector. Default: NxxxZ000FAN CBE: Program this with the logic equation programming for the fan. This equation will con-tain CBE programming that will initiate the fan stopping or starting. Default: NxxxZ000LATCHING FIRE MODE: Select Yes or No to defines whether or not the start relay (pro-grammed in FAN START POINT) will remain latched when an alarm occurs. If set to Yes, a systemreset will not affect SCS operation. Default: NoDELAY FAULT STATUS: Delay fault status reporting to the panel for current monitoring relays.(Select 0 to 180 seconds) Default: 35 secondsUSE SINGLE START/STOP: Select Yes or No to define whether or not a single relay moduleaddress will be used to start and stop the fan. Default: NoACTIVE ON CBE: Select START or STOP. If set to START, the FAN START POINT will beactivated when the FAN CBE goes active. If set to STOP, the FAN STOP POINT will be activatedwhen the FAN CBE goes active. Default: StartH.4 Basic Programming: General and Logic ZonesWhen using smoke control on the AFP-3030, General Zone and Logic Equation programming isrequired for some configurations.General ZonesThe Duct Detector Zone is defined as a general zone used by one or more duct detectors, if ductdetectors are being utilized in the system. The Duct Detector Zone should be programmed withNon-resettable Control, Silenceable, and Precedence Participation set to NO.When using duct detectors and a Duct Detector Zone, logic zone programming may be required tostop and stop the fan, depending on configuration settings.Logic ZonesTwo to three logic zones are required when using duct detectors in the Smoke Control system.Basic programming of the ZLduct, ZLstart, and ZLstop logic zones are defined below. Refer to theSection H.6 on page 136 for configuration information.ZLduct = DEL(00:01:00,**.**.**,NOT(Zxxx)), where the first time is the extent ofdelay time and Zxxx is the duct detector zone.ZLduct will be the first CBE zone of the duct detector.