Settings42 KW2M-A/X User's Manual5.5.3 Settings for Demand and Power RatesClick ‘ ’ to shift window of ‘Demand Setup’ and ‘Conversion rate Setup’.[Demand Setup]Item Description1 Power demand type Select type of power demand measurement.
Sliding block, Fixed block (initial: Sliding block)2 Power demand interval Set interval time to use for power demand measurement.Power demand interval 1: 1 to 60min (initial: 15)Power demand interval 2: 1 to 60min (initial: 1)3 Power input source *1 Select input type to use for demand measurement, currentmeasurement or pulse input.
CT, Pulse (initial: CT)4 Pulse-Power ConversionMethod *2Select and set electric power value per 1-pulse or pulseconstant value input by an outer pulse detector.Pulse rate: 0.001 to 100.000 kWh/pulse (initial: 0.001)Pulse constant: 1000 to 99000 pulse/kWh (initial: 50000)5 Current demand interval Set interval to use for current demand calculation.< Range >1 to 60min (initial: 15)*1 Power input source is setting for main unit CH1.*2 Pulse-power conversion method is available when [Pulse] is selected for ‘Power input source’.12345