Settings46 KW2M-A/X User's Manual[Alarm]The alarm is output when the condition next to a checked (activated) box is true.Item Description1 Select CH * Select channel to set.2 Output type Select pulse output type.< List >Integral power pulse, Alarm, General output(initial: Integral power pulse)3 Stand-by power Select phase to monitor and set the threshold to use for output.
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)Threshold: 0.1 to 100.0% (initial: 0.1%)Elapsed: 0 to 9999min (initial: 0)4 Active power Select phase to monitor and set the threshold to use for output.*Select ‘Total’ when measuring 3P3W.
Target phase: Phase1, Phase2, Phase3, ALL, Total(initial: Total)OFF threshold: 0.00 to 9999999999.99 (initial: 9999999999.99)ON threshold: 0.00 to 9999999999.99 (initial: 9999999999.99)5 Reactive power6 Apparent power7 Over current Select phase to monitor.*The threshold is the ratio that is set at ‘Setting for PowerMeasurement’.< List >Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)8 Under current9 Power interruption345678910112223202118191617141512 1312