SettingsKW2M-A/X User's Manual 455.5.5 Settings for Pulse OutputThe measurement value of main unit CH1 is used fo for pulse output CH1 and the measurement value ofmain unit CH2 is used for pulse output CH2.[Integral power pulse]Item Description1 Select CH * Select channel to set.2 Output type Select pulse output type.< List >Integral power pulse, Alarm, General output(initial: Integral power pulse)3 Unit for output Set unit used for pulse output.< List >0.001, 0.01, 0.1, 1, 10, 100kWh (initial: 0.001)4 Direction Select direction of power (import or export) to be used as athreshold for pulse output.< List >P, -P (initial: P)5 Target phase Select a phase to monitor in order to judge the output.Select ‘Total’ for measuring 3P3W.< List >Phase1, Phase2, Phase3, Total (initial: Total)6 Pulse width Set pulse width.< Range >1 to 100ms (initial: 1)123456