Specifications84 KW2M-A/X User's Manual11.3 Output Specifications (main unit only)Number of outputs 2 (insulate between output terminals)Insulation method MOSFET relayOutput type 1aOutput capacity 100mA, 30V AC/DCOutput mode (OUT1/OUT2) ・Pulse by integral power・Output by alarm or events (set in setting mode)Pulse by integralpowerPulse width 1 to 100ms (set in setting mode)Pulse outputunit 0.001kWh/ 0.01kWh/ 0.1kWh/ 1kWh/ 10kWh/ 100kWhAlarmEventTypeStand-by alarm/ Under voltage alarm/ Over voltagealarm/Power interruption alarm/ Under current alarm/Overcurrent alarm/ Active power alarm/ Reactive poweralarm/Apparent power alarm/ PF alarm/ Over frequency alarm/Under frequency alarm/ Voltage harmonics alarm/ Currentharmonics alarm/ Voltage THD alarm/ Current THD alarm/Unbalanced voltage alarm/ Unbalanced current alarm/ Powerdemand alarm/ Current demand alarm/ counter output/ leveloutput (external control)Alarm reset Self-reset (according to the setting) / Manual-resetProtection element VaristorAlarm outputIndicator Lighting alarm mark and blinking backlightOutput signal 2 (can be set separately)Normal: OFF, Alarm: ONOutput capacity 100mA, 30V AC/DC