60 | City Series CC40EPVinstallation920-040 02.13.192CITY SERIES15. Reinstall pilot cap and pilot retainer clip.16. Prior to installing burner—adjust aerations settings - to 1/4" forLP.(CB40E/CC40E/CV40E/CB40EPV/CV40EPV/CC40EPV) or 3/8"(CB40E-1/CC40E-1/CV40E-1) Reinstall burner (see Step 13).17. Ensure the pilot light is in the correct orientation to the Burner. Recon-nect the gas and electrical supply to the appliance. Start the appliance.(see section on Lighting Instructions) Ensure that pilot and burner igni-tion is completed without delay. Check both your inlet and outlet pres-sures at full load. With a soapy solution, leak test the entire system.Verify both the correct flame and pilot appearance.18. See Gas Pipe Pressure Testing in manual.13. Remove pilot retainer clip with pliers and pull off the pilot cap to exposethe pilot orifice.14. Unscrew the pilot orifice with the allen key; then replace with the LPGpilot orifice and the pilot cap, provided in the kit.Installer Notice:These instructions must be leftwith the appliance.Pilot retainer clip12. Remove burner orifice with a 3/8" wrench. Use another wrench to holdon to the elbow behind the orifice. Discard orifice. Reinstall new burnerorifice LPG stamped #53 and tighten.Burner OrificeLocationCV40E shown11. Loosen 4 screws in locations shown below (2 at front and 2 at rear)—slideburner to the left away from the orifice and lift out.frontscrew locationsback screw locationsCity SeriesLP SYSTEM DATAMin. Supply Pressure 11" WC (2.73kpa)Manifold Pressure - High 10.5" WC (2.62 kpa)Manifold Pressure - Low 2.9" WC (0.72 kpa)Orifice Size #53 DMSMaximum Input 28,500 Btu/h (8.35 kW)Minimum Input 15,500 Btu/h (4.54 KW)Altitude 0-4500 ft (0-1372m)