5.14 GROUP 3.14: MULTIPUMPTable 42: Multipump parametersIndex Parameter Min Max Unit Default ID DescriptionP3.14.1 Number of Motors 1 5 1 1001The quantity of motors(or pumps or fans) thatthere are in the multi-pump system.P3.14.2Interlock Function 0 1 1 1032Enable or disable theinterlocks. You can usethe interlocks to tellthe system if a motor isconnected.0 = Disabled1 = EnabledP3.14.3Include FC 0 1 1 1028Include the AC drive inthe autochange andinterlock system.0 = Disabled1 = EnabledP3.14.4Autochange 0 1 1 1027Enable or disable therotation of the startsequence and the pri-ority of motors.0 = Disabled1 = EnabledP3.14.5 Autochange Interval 0.0 3000.0 h 48.0 1029When this time is over,the autochange occursif the capacity is belowthe level set withP3.14.6. and P3.14.7.P3.14.6 Autochange: Fre-quency Limit 0.00 50.00 Hz 25.00 1031 These parametersdefine the level belowwhich the capacitymust stay for theautochange to occur.P3.14.7 Autochange: MotorLimit 0 4 1 1030P3.14.8 Bandwidth 0 100 % 10 1097The percentage of thesetpoint. For example,if setpoint = 5 bar,bandwidth = 10%.When the feedbackvalue stays between4.5 and 5.5 bar, themotor is not discon-nected or removed.VACON · 102 PARAMETERS MENU5 TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205