5 If the digital input DI6 was already used for someother function, a message scrolls on the display.Change one of these selections.READY FAULTALARMSTOPRUNKEYPAD1/OREVFWD BUSAfter the steps, a digital signal to the digital input DI6 controls the function External FaultClose.The value of a function can be DigIN Slot0.1 (in the graphical display) or dI 0.1 (in the textdisplay). In these conditions, you did not give a terminal to the function, or the the input wasset to be always OPEN. This is the default value of most of parameters in the group M3.5.1.On the other hand, some inputs have the default value always CLOSED. Their value showsDigIN Slot0.2 in the graphical display and dI 0.2 in the text display.NOTE!You can also give time channels to digital inputs. There is more data about it inTable Table 14 Digital input settings.9.5.1.2 Descriptions of signal sourcesSource FunctionSlot01 = Always OPEN2-9 = Always CLOSEDSlotA Number agrees to a digital input in slot A.SlotB Number agrees to a digital input in slot B.SlotC Number agrees to a digital input in slot C.SlotD Number agrees to a digital input in slot D.SlotE Number agrees to a digital input in slot E.TimeChannel (tCh) 1=Time Channel1, 2=Time Channel2, 3=Time Channel39.5.2 DIGITAL INPUTSThe parameters are functions that you can connect to a digital input terminal. The text DigInSlot A.2 means the second input on the slot A. It is also possible to connect the functions totime channels. The time channels work as terminals.You can monitor the statuses of the digital inputs and the digital outputs in theMultimonitoring view.VACON · 140 PARAMETER DESCRIPTIONS9 TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205