4.1.5 PID2 CONTROLLER MONITORINGTable 6: Monitoring of the values of the PID2 controllerIndex Monitoring value Unit ID DescriptionV2.5.1 PID2 setpoint Varies 83The setpoint value of the PID2 controller in proc-ess units. You can use a parameter to make theselection of the process unit.V2.5.2 PID2 feedback Varies 84The feedback value of the PID2 controller in proc-ess units. You can use a parameter to make theselection of the process unit.V2.5.3 PID2 error value Varies 85The error value of the PID2 controller. It is thedeviation of feedback from the setpoint in processunits. You can use a parameter to make the selec-tion of the process unit.V2.5.4 PID2 output % 86The PID2 controller output as a percentage(0-100%). It is possible to give this value to, forexample, the analogue output.V2.5.5 PID2 status 870=Stopped1=Running2=In dead band (see Chapter 5.13 Group 3.13: PID-controller 2)4.1.6 MULTI-PUMP MONITORINGTable 7: Multipump monitoringIndex Monitoring value Unit ID DescriptionV2.6.1 Motors running 30 The number of motors that operate when theMulti-pump function is used.V2.6.2 Autochange 1114 The system tells you if an autochange is neces-sary.MONITORING MENU VACON · 5124-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM 4