Interval 2P3.11.2.1: ON Time: 09:00:00P3.11.2.2: OFF Time: 13:00:00P3.11.2.3: From Day: SaturdayP3.11.2.4: To Day: SundayP3.11.2.5: Assign to channel: Time channel 1Timer 1You can start the motor with the digital input 1 on slot A during other times than thosespecified with the intervals. In this case, the timer specifies the duration that the motor runs.P3.11.6.1: Duration: 1800 s (30 min)P3.11.6.2: Assign to channel: Time channel 1P3.5.1.18: Timer 1: DigIn SlotA.1 (The parameter located in the digital inputs menu)Interval 1ON = 07:00:00 hrs OFF = 17:00:00 hrsInterval 2From = Saturday To = SundayFrom = Monday To = FridayON = 09:00:00 hrs OFF = 13:00:00 hrsP Ctrl Signal 1ADigital input 1on Slot A Timer 1Duration = 1800 sTime channel 1 Start/StopFig. 32: Time channel 1 is used as the control signal for the start command instead of a digitalinput9.10 PID CONTROLLER 1P3.13.1.9 DEAD BAND HYSTERESIS (ID 1056)9.10.1 SETPOINTSP3.12.2.8 SLEEP DELAY 1 (ID1017)See the description of parameter P3.12.2.10.P3.12.2.9 WAKE-UP LEVEL 1 (ID1018)See the description of parameter P3.12.2.10.P3.12.2.10 SP1 WAKE-UP MODE (ID 15539)With these parameters, you can set when the drive wakes up from the sleep mode.The drive wakes up from the sleep mode when the value of PID Feedback goes below theWake-up level.VACON · 154 PARAMETER DESCRIPTIONS9 TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205