5.3 GROUP 3.3: CONTROL REFERENCE SETTINGSTable 12: Control reference settingsIndex Parameter Min Max Unit Default ID DescriptionP3.3.1 Minimum Frequency 0.00 P3.3.2 Hz 0.00 101 The minimum fre-quency referenceP3.3.2 Maximum Frequency P3.3.1 320.00 Hz 50.00 102 The maximum fre-quency referenceP3.3.3 I/O Control Refer-ence A Selection 1 11 6 117Selection of the refer-ence source when thecontrol place is I/O A.1 = Preset Frequency 02 = Keypad reference3 = Fieldbus4 = AI15 = AI26 = AI1+AI27 = PID 1 reference8 = Motor potentiome-ter9 = Average (AI1, AI2)10 = Min (AI1, AI2)12 = Max (AI1, AI2)P3.3.4 I/O Control Refer-ence B Selection 1 10 4 131Selection of the refer-ence source when thecontrol place is I/O B.See above. You canforce the I/O B controlplace to be active onlywith a digital input(P3.5.1.5).P3.3.5 Keypad Ctrl Refer-ence Selection 1 8 2 121Selection of the refer-ence source when thecontrol place is keypad.1 = Preset Frequency 02 = Keypad3 = Fieldbus4 = AI15 = AI26 = AI1+AI27 = PID 1 reference8 = Motor potentiome-terP3.3.6 Keypad Reference 0.00 P3.3.2 Hz 0.00 184You can adjust the fre-quency reference onthe keypad with thisparameter.PARAMETERS MENU VACON · 6124-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM 5