5.6 GROUP 3.6: FIELDBUS DATA MAPPINGTable 18: Fieldbus data mappingIndex Parameter Min Max Unit Default ID DescriptionP3.6.1 Fieldbus Data Out 1Selection 0 35000 1 852Make the selection ofthe data that is sent tofieldbus with the ID ofthe parameter or mon-itor. The data is scaledto an unsigned 16-bitformat according to theformat on the controlpanel. For example,25.5 on the displayagrees with 255.P3.6.2 Fieldbus Data Out 2Selection 0 35000 2 853Make the selection ofthe Process Data Outwith the parameter ID.P3.6.3 Fieldbus Data Out 3Selection 0 35000 45 854Make the selection ofthe Process Data Outwith the parameter ID.P3.6.4 Fieldbus Data Out 4Selection 0 35000 4 855Make the selection ofthe Process Data Outwith the parameter ID.P3.6.5 Fieldbus Data Out 5Selection 0 35000 5 856Make the selection ofthe Process Data Outwith the parameter ID.P3.6.6 Fieldbus Data Out 6Selection 0 35000 6 857Make the selection ofthe Process Data Outwith the parameter ID.P3.6.7 Fieldbus Data Out 7Selection 0 35000 7 858Make the selection ofthe Process Data Outwith the parameter ID.P3.6.8 Fieldbus Data Out 8Selection 0 35000 37 859Make the selection ofthe Process Data Outwith the parameter ID.PARAMETERS MENU VACON · 7724-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM 5