9Set the signal range of the analogue input0 = 0-10V / 0-20mA1 = 2-10V / 4-20mASee Table 15 Analogue input settings.10 Set a value for Keypad Setpoint 1 (P3.12.2.1) andKeypad Setpoint 2 (P3.12.2.2)Depends on the range set in the question 9.11Using the sleep function0 = No1 = YesIf you give the value Yes for the question 11, you see the next 3 questions. If you give the valueNo, the wizard is completed.12 Set a value for Sleep Frequency Limit (P3.12.2.7) Range: 0.00-320.00 Hz13 Set a value for Sleep Delay 1 (P3.12.2.8) Range: 0-3000 s14 Set a value for Wake-up Level (P3.12.2.9) The range depends on the set process unitThe PID mini-wizard is completed.2.2 MULTI-PUMP MINI-WIZARDThe Multi-pump mini-wizard asks the most important questions to set up a Multi-pumpsystem. The Multi-pump mini-wizard always follows the PID mini-wizard.15 Set a value for Number of Motors (P.3.14.1) 1-416Set a value for Interlock Function (P3.14.2)0 = Not used1 = Enabled17Set a value for Autochange (P3.14.4)0 = Disabled1 = EnabledIf you enable the Autochange function, you see the next 3 questions. If you do not use theAutochange function, the wizard goes directly to question 21.VACON · 20 WIZARDS2 TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205