5.4 GROUP 3.4: RAMP AND BRAKES SETUPTable 13: Ramp and brakes setupIndex Parameter Min Max Unit Default ID DescriptionP3.4.1Ramp 1 Shape 0.0 10.0 s 0.0 500You can makesmoother the start andthe end of the acceler-ation and decelerationramps.P3.4.2 Acceleration Time 1 0.1 3000.0 s 20.0 103Gives the time that isnecessary for the out-put frequency toincrease from zero fre-quency to maximumfrequency.P3.4.3 Deceleration Time 1 0.1 3000.0 s 20.0 104Gives the time that isnecessary for the out-put frequency todecrease from maxi-mum frequency to zerofrequency.P3.4.4 Ramp 2 Shape 0.0 10.0 s 0.0 501You can makesmoother the start andthe end of the acceler-ation and decelerationramps.P3.4.5 Acceleration Time 2 0.1 3000.0 s 20.0 502Gives the time that isnecessary for the out-put frequency toincrease from zero fre-quency to maximumfrequency.P3.4.6 Deceleration Time 2 0.1 3000.0 s 20.0 503Gives the time that isnecessary for the out-put frequency todecrease from maxi-mum frequency to zerofrequency.P3.4.7 Start MagnetisingTime 0.00 600.00 s 0.00 516Gives the time duringwhich the DC current isfed to the motor beforethe acceleration starts.P3.4.8 Start MagnetisingCurrent Varies Varies A Varies 517P3.4.9 DC Braking Time atStop 0.00 600.00 s 0.00 508Tells if the braking isON or OFF and givesthe braking time whenthe motor stops.PARAMETERS MENU VACON · 6524-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM 5