150 • EtherNet/IP (Ethernet/Industrial Protocol)Object modelWAGO-I/O-SYSTEM 750ETHERNET TCP/IP4.3.3.2.3 Explanations of the Object DescriptionAttribute ID: Integer value which is assigned to the corresponded attributeAccess: Set The attribute can be accessed by means of Set_Attribute services.Important: All the set attributes can also be accessed by means ofGet_Attribute services.Get The attribute can be accessed by means of Get_Attribute servicesNV: NV (non volatile) The attribute is permanently stored in the coupler.V (volatile) The attribute is not permanently stored in the coupler.Note: If this column is missing, all attributes have the type VName: Designation of the attributeData type: Designation of the CIP data type of the attributeDescription: Short description for the AttributeDefault value: Factory settings4.3.3.2.4 Identity (01 hex)ClassAttributeID Access Name Data type Description Defaultvalue1 Get Revision UINT Revision of this object 1 (0x0001)2 Get Max Instance UINT Maximum Instance 0x00013 Get Max ID Numberof ClassAttributesUINT Maximum number of Classattributes0x00004 Get Max ID Numberof InstanceAttributeUINT Maximum number of instanceattributes0x0000Instance 1AttributeIDAccess Name Data type Description Default value1 Get Vendor ID UINT Manufacturer identification 40 (0x0028)2 Get Device Type UINT General type designation ofthe product12 (0x000C)3 Get Product Code UINT Designation of the coupler e.g. 341 (0x0155)Revision STRUCT of:Major Revision USINT4 GetMinor Revision USINTRevision of the IdentityObjectsDepending on thefirmware