Power Supply • 25IsolationWAGO-I/O-SYSTEM 750ETHERNET TCP/IP2.7 Power Supply2.7.1 IsolationWithin the fieldbus node, there are three electrically isolated potentials.• Operational voltage for the fieldbus interface.• Electronics of the couplers/controllers and the bus modules (internal bus).• All bus modules have an electrical isolation between the electronics(internal bus, logic) and the field electronics. Some digital and analoginput modules have each channel electrically isolated, please see catalog.Fig. 2-10: Isolation g0xxx01eAttentionThe ground wire connection must be present in each group. In order that allprotective conductor functions are maintained under all circumstances, it isrecommended that a ground wire be connected at the beginning and end of apotential group. (ring format, please see chapter "2.8.3"). Thus, if a busmodule comes loose from a composite during servicing, then the protectiveconductor connection is still guaranteed for all connected field devices.When using a joint power supply unit for the 24 V system supply and the24 V field supply, the electrical isolation between the internal bus and thefield level is eliminated for the potential group.