24 • The WAGO-I/O-SYSTEM 750Mechanical SetupWAGO-I/O-SYSTEM 750ETHERNET TCP/IP2.6.9 Wire connectionAll components have CAGE CLAMP® connections.The WAGO CAGE CLAMP® connection is appropriate for solid, strandedand fine–stranded conductors. Each clamping unit accommodates oneconductor.Fig. 2-9: CAGE CLAMP® Connection g0xxx08xThe operating tool is inserted into the opening above the connection. Thisopens the CAGE CLAMP®. Subsequently the conductor can be inserted intothe opening. After removing the operating tool, the conductor is safelyclamped.More than one conductor per connection is not permissible. If severalconductors have to be made at one connection point, then they should be madeaway from the connection point using WAGO Terminal Blocks. The terminalblocks may be jumpered together and a single wire brought back to the I/Omodule connection point.AttentionIf it is unavoidable to jointly connect 2 conductors, then a ferrule must beused to join the wires together.Ferrule:Length 8 mmNominal cross sectionmax. 1 mm2 for 2 conductors with 0.5 mm2eachWAGO Product 216-103or products with comparable properties