WAGO-I/O-SYSTEM 750 Commissioning 101750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iParManualVersion 1.2.0, valid from HW/SW Version 01/017.4.5 Adjustable ParametersTable 26: Adjustable parametersParameter name Value rangeInput filter time 0 ms (off) / 0.2 ms / 0.5 ms / 1 ms / 2 ms / 3 ms* /5 ms / 10 ms / 20 ms / 50 ms / 100 ms / 200 msShort-circuit test I1 Inactive / Active*Short-circuit test I2 Inactive / Active*Short-circuit test I3 Inactive / Active*Short-circuit test I4 Inactive / Active*Two-channel analysisI1 & I2 Yes/No*Two-channel analysisI3 & I4 Yes/No*Discrepancy time I1 & I2 10 ms ... 100 ms* ... 65535 msDiscrepancy time I3 & I4 10 ms ... 100 ms* ... 65535 msValence analysis I1 & I2 Equivalent* / AntivalentValence analysis I3 & I4 Equivalent* / AntivalentRestart barrier I1 & I2 Yes* / NoRestart barrier I3 & I4 Yes* / NoOperating mode of the inputchannelsStandard analysis* /Rotary table, i.e. all safe inputs I1 ... I4 aresensitive to T1Output Configuration H-Side/L-Side 1* / H-Side/L-Side 2 /H-Side/H-Side 1 / H-Side/H-Side 2Line break detection Inactive* / ActiveTest pulse duration O10 ms (off) / 2 ms / 5 ms* / 10 ms / 20 ms /50 ms / 100 ms / 150 ms / 200 ms / 250 ms /300 ms / 350 ms / 400 ms / 450 ms / 500 msTest pulse duration O20 ms (off) / 2 ms / 5 ms* / 10 ms / 20 ms /50 ms / 100 ms / 150 ms / 200 ms / 250 ms /300 ms / 350 ms / 400 ms / 450 ms / 500 msOutput toerlance time O12 ms / 5 ms / 10 ms / 20 ms / 30 ms* / 50 ms /100 ms / 150 ms / 200 ms / 250 ms / 300 ms /350 ms / 400 ms / 450 ms / 500 msOutput tolerance time O22 ms / 5 ms / 10 ms / 20 ms / 30 ms* / 50 ms /100 ms / 150 ms / 200 ms / 250 ms / 300 ms /350 ms / 400 ms / 450 ms / 500 ms* Standard setting