WAGO-I/O-SYSTEM 750 Process Image 123750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iParManualVersion 1.2.0, valid from HW/SW Version 01/018.2 PROFIsafe V2 ModeTable 37: Process image PROFIsafe V2 modeInput data Output dataByte 0 PROFIsafe Inputs Byte 0 PROFIsafe OutputsByte 1 PROFIsafe status Byte 1 PROFIsafe statusByte 2 PROFIsafe CRC2 Byte 2 Byte 2 PROFIsafe CRC2 Byte 2Byte 3 PROFIsafe CRC2 Byte 1 Byte 3 PROFIsafe CRC2 Byte 1Byte 4 PROFIsafe CRC2 Byte 0 Byte 4 PROFIsafe CRC2 Byte 0Byte 0 ... Byte 4 Secure process data (PROFIsafe telegram)Table 38: PROFIsafe inputs, V2 modeBit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0X X X X I 4 I 3 I 2 I 1I 1 Signal state I 1 – Digital input channel 1I 2 Signal state I 2 – Digital input channel 2I 3 Signal state I 3 – Digital input channel 3I 4 Signal state I 4 – Digital input channel 4X This bit is reserved and may not be evaluated.Table 39: PROFIsafe outputs, V2 mode, output configuration „H-Side/L-Side 2“ or„H-Side/H-Side 2“Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 0 0 0 0 0 O 2 O 1O 1 Signal state O 1 – Digital output channel 1O 2 Signal state O 2 – Digital output channel 20 This bit is reserved and may not be changed.Table 40: PROFIsafe outputs, V2 mode, output configuration „H-Side/L-Side 1“ or„H-Side/H-Side 1“Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 0 0 0 0 0 0 O 1/O 2O 1/O 2 Signal state O 1/O 2– Digital output channel 1 and channel 20 This bit is reserved and may not be changed.