32 Device Description WAGO-I/O-SYSTEM 750750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iParManualVersion 1.2.0, valid from HW/SW Version 01/014.6 Technical Data4.6.1 Device DataTable 11: Technical data, deviceDimensions B x W* x D(* from upper edge of rail)24 mm x 64 mm x 100 mmWeight approx. 100 g4.6.2 SupplyTable 12: Technical data, supplyPower supply Via system voltage internal bus (5 VDC) and power jumper contacts (24 VDC)Overvoltage categoryacc. EN61131-2IIRate voltage, field voltage supply 24 V DC (20.4 V ... 31.2 V DC)Current consumption, system voltage typ.(5 V DC)190 mACurrent consumption, power jumpercontacts typ.(24 V DC)40 mACurrent consumption for digital poweroutput suply X2.1 typ.(24 V DC)30 mA + load currentRated current via power jumper contacts(right)10 AReverse polarity protection, field voltagesupplyyesIsolation: 500 V system voltage / field level(power jumper contacts)