WAGO-I/O-SYSTEM 750 Connect Devices 87750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iParManualVersion 1.2.0, valid from HW/SW Version 01/01Figure 43: Connection variant with 2 diode recovery circuitsIn the output configuration H-Side/L-ide 2, you can connect an inductive loadbetween connection O1B to the common (ground) connection of the field supplyvoltage 0V and/or a second inductive load between connection O2A to thepositive connection of the field supply voltage 24V.In this case, pay attention to the voltage values listed in the table when selectingthe external diode recovery circuit.Table 25: Maximum negative voltage of the diode recovery circuit, output configuration H-Side/L-Side 2Field Voltage ULx+19.2V -31V+24.0V -26V+26.4V -24V+28.8V -21V+31.2V -19V