Application Overview 2-7# VFD Object Configuration Property SummaryTable 2.4 - VFD Object Configuration Property SummaryProperty Name Variable Type Default Parameter DescriptionnciNmlSpeed SNVT_rpm 1800 rpm n/a Configures nominal motor speed in rpmnciNmlFreq SNVT_freq_hz 60Hz n/a Configures nominal motor frequency in hertz All speed related data in percent are referencedto this valuenciMinSpeed SNVT_lev_percent 0% d2-02 Configures the minimum motor speed as a percentage of nciNmlFreq Sets the driveís lowerlimit for frequency commandsnciMaxSpeed SNVT_lev_percent 100% d2-01 Configures the maximum motor speed as a percentage of nciNmlFreq Sets the driveís upperlimit for frequency commandsnciRampUpTm SNVT_time_sec 10sec C1-01 Configures motor ramp up time from 0 to its operating setpoint Sets the driveís outputacceleration ratenciRampDownTm SNVT_time_sec 10sec C1-02 Configures motor ramp down time from its operating setpoint to 0 Sets the driveís outputdeceleration ratenciSndHrtBt SNVT_time_sec 0sec (off) n/a Configures the maximum period of time that expires before automatic propagation ofnvoDrvCurnt nvoDrvSpeed nvoDrvVolt and nvoDrvPwrnciRcvHrtBt SNVT_time_sec 0sec (off) n/a Configures the maximum period of time that expires between network variable updatesbefore a cable loss condition is declared and the drive is stoppednciMinOutTm SNVT_time_sec 1sec n/a Configures the minimum period of time that expires before changes in output networkvariables are propagatednciLocation SNVT_str_asc All ì\0î n/a Available for a description of the physical location of the nodenciDrvSpeedScale SNVT_lev_percent 100% n/a Scales the speed setpoint nviDrvSpeedStpt (saved configured value)nciOpModeRun SNVT_count 1 b1-02 Selects the source for start/stop and speed commandsnciDrvMaxFreq SNVT_freq_hz 60.0Hz E1-04 Reports the maximum output frequency of the drive (read-only)nciMtrFLA SNVT_amp * E2-01 Sets the full load current rating of the motornciPLRideThru SNVT_count 2.0sec L2-02 Selects the driveís response to momentary power loss ride through timenciAutoRstrt SNVT_count 0 L5-01 Selects the number of times the drive attempts to automatically restart after certain faultsnciProFreq1 SNVT_freq_hz 0Hz d3-01 Sets the center frequency for the first band of prohibit frequenciesnciProFreq2 SNVT_freq_hz 0Hz d3-02 Sets the center frequency for the second band of prohibit frequenciesnciProFreqBW SNVT_freq_hz 1.0Hz d3-04 Sets the bandwidth for prohibit frequenciesnciPIDSel SNVT_count 0 b5-01 Selects the mode of the PID controllernciPID_PGain SNVT_multiplier 20 b5-02 Sets the proportional gain of the PID controllernciPID_ITime SNVT_time_sec 5.0sec b5-03 Sets the integral time constant of the PID controllernvoDrvRatedCur SNVT_amp * n9-01 Reports the output current rating of the drive (read-only)nciStallLevAcc SNVT_count * L3-02 Sets the stall level for output current during accelerationnciStallLevRun SNVT_count * L3-06 Sets the stall level for output current while at set speednciCblLossSpeed SNVT_lev_percent 0% n/a Sets speed level commanded if network communication is lostnciCblLossFltEna SNVT_switch Off n/a Enables an EF0 fault to be declared if network communication is lostnciOpModeFreqRef SNVT_count 1 b1-01 Selects frequency reference source* - Value dependent on drive capacity. Refer to appropriate Parameter Access and/or Technical Manual.