Application Overview 2-12# Operational Mode – nciOpModeRunTable 2.10 - Operational Mode - nciOpModeRunProperty Name Variable Type Default Parameter DescriptionnciOpModeRun SNVT_count 0 b1-02 Selects location of the Run/Stop commandTable 2.11 - nciOpModeRunnciOpModeRun Run Command Source Remarks0 Digital Operator nviDrvSpeedStpt has no effect1 External Terminals nviDrvSpeedStpt has no effect2 Serial Communications (L ON W ORKS) nviDrvSpeedStpt is controlled via the network3 Option Card nviDrvSpeedStpt has no effect# Operational Mode – nciOpModeFreqRefTable 2.12 - Operational Mode - nciOpModeRunProperty Name Variable Type Default Parameter DescriptionnciOpModeFreqRef SNVT_count 0 b1-01 Selects location of the frequency reference commandTable 2.13 - nciOpModeFreqRefnciOpModeFreqRef Run Command Source Remarks0 Digital Operator nviDrvSpeedScale has no effect1 External Terminals nviDrvSpeedScale has no effect2 Serial Communications (L ON W ORKS) nviDrvSpeedScale is controlled via the network3 Option Card nviDrvSpeedScale has no effect4 Pulse Input nviDrvSpeedScale has no effect (Available on F7 and G7 only)# Motor Properties – nciNmlSpeed, nciNmlFreq, nciMaxSpeed, nciMinSpeed,nciMtrFLAThese properties define the motor characteristics, configuring the drive as described below:Table 2.13 - Motor Properties – nciNmlSpeed, nciNmlFreq, nciMaxSpeed, nciMinSpeed, nciMtrFLAProperty Name Variable Type Default Parameter DescriptionnciNmlSpeed SNVT_rpm 1800 rpm n/a Configures nominal motor speed in rpm.nciNmlFreq SNVT_freq_hz 60 Hz n/a Configures nominal motor frequency in hertz. All speed related data inpercent are referenced to this value.nciMinSpeed SNVT_lev_percent 0% d2-02 Configures the minimum motor speed as a percentage of nciNmlFreq. Setsthe driveís lower limit for frequency commands.nciMaxSpeed SNVT_lev_percent 100% d2-01 Configures the maximum motor speed as a percentage of nciNmlFreq.Sets the driveís upper limit for frequency commands.nciMtrFLA SNVT_amp * E2-01 Sets the full load current rating of the motor.* Value is dependent on drive capacity. Refer to appropriate parameter access and/or technical manual.