Diagnostics 3-8# Drive Parameters are Set CorrectlyThe LONW ORKS Option communicates with the drive via RS485. It is necessary to set the drive communications parameters to match those of theLONW ORKS Option.Table 3.1 – Drive Parameter SettingsParameter Function Data +/- Limits - Description Default0 Operator1 UserA1-01 Access Level2 Advanced (L ON WORKS)2H5-01 Serial Communications Address 1F 0 ñ 1Fh (0 ñ 31 dec) 1Fh0 1200 baud1 2400 baud2 4800 baud3 9600 baud (L ON WORKS)H5-02 Serial Baud Rate Select4 19200 baud30 None (L ON WORKS)1 Even parityH5-03 Serial Parity Select2 Odd parity0H5-06 Transmit Wait 5 5 ñ 65ms 50 Disabled (LON WORKS)H5-07 RTS Control Select 1 Enabled 00 MODBUS (L ON WORKS)1 N2 (Metasys) (E7, E7L and E7B only)H5-08 Protocol Select2 P1 (APOGEE) (E7, E7L and E7B only)0It is also necessary to set the control parameters to the application requirements.Table 3.2 – Control ParametersParameter Function Value Description Default0 Operator Keypad1 External Terminals2 Serial Communications (L ON WORKS)3 Option PCBb1-01 Frequency Reference Source4 Pulse input (Available on F7 and G7 drives only)00 Operator keypad1 Terminals2 Serial Communications (L ON WORKS)b1-02 Run/Stop Command Source3 Option PCB00 Ramp to Stop1 Coast to Stop2 Emergency Stop (Decel time set by C1-09)F6-01 Stopping Method for CommunicationsError3 Operation Continues10 Always detectF6-02 External Fault Detection 1 Detect During Operation 00 Ramp to Stop1 Coast to Stop2 Emergency Stop (Decel time set by C1-09)F6-03 Stopping Method for External Fault3 Operation Continues1