3.2 Function Modules3.2.4 The M-EXECUTOR3-573 CPU Module FunctionalityM-EXECUTOR Detail SettingsThe detailed settings for the M-EXECUTOR are performed on the Module Configuration TabPage and the Detail Definition Dialog Box.This section provides the procedures to display this tab page and dialog box, and describes their contents. Module Configuration Definition Tab PageUse the following procedure to display the Module Configuration Definition Tab Page.• Click the Module Configuration Icon on the Start Tab Page.The following table describes the M-EXECUTOR items that are displayed on the Module Con-figuration Definition Tab Page.No. Item Display/Setting Item Editing Function Module/SlaveDisplays whether the M-EXECUTOR is enabled.• UNDEFINED: Disabled• M-EXECUTOR: EnabledPossible Status Displays the status of the M-EXECUTOR. Possible Circuit No./Axis AddressStart Not used.“----” is always displayed. Not possibleOccupiedcircuits Motion Register Not used.“----” is always displayed. Not possibleRegister(Input/Output)Disabled Not used.“----” is always displayed. Not possible Start- EndDisplays the range of registers that is used as the I/O area.• Setting range: 00000 to 07FFF hex or 10000 to 17FFF hexRefer to the following section for details. Details on the I/O Registers on page 3-58Possible SizeThe size of the I/O area is displayed in words.• Setting range: 64 to 128Four words each of input registers and output registers arerequired to register a single motion program or sequence pro-gram in the M-EXECUTOR. If you need to register more than16 programs, set the size with four additional words for eachprogram to add. A maximum of 32 programs can be regis-tered (maximum number of program definitions).Possible Scan Not used.“----” is always displayed. Not possible Comment Display the user comment.Enter a comment of up to 16 characters. PossibleCells forM-EXEC-UTORsettings