YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 439 Option Drive Parameters9 Option Drive ParametersBefore starting network communications, verify proper setting of drive parameters inTable 10 using the drive digital operator.Table 10 Parameter SettingsNo. Name Description Defaultb1-01<1>Frequency ReferenceSelectionSelects the frequency reference input source.0: Operator - Digital preset speed d1-01 to d1-171: Terminals - Analog input terminal A1 or A22: MEMOBUS/Modbus communications3: Option PCB4: Pulse Input (Terminal RP)1(Set to 3 forPROFINET)b1-02<1> Run Command SelectionSelects the run command input source.0: Digital Operator - RUN and STOP keys1: Digital input terminals S1 to S72: MEMOBUS/Modbus communications3: Option PCB1(Set to 3 forPROFINET)F6-01 Operation Selection afterCommunications ErrorDetermines drive response when a bUS error isdetected during communications with the option.0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only <2>4: Alarm (d1-04) <5>5: Alarm Ramp to Stop <5>1F6-02 External Fault DetectionConditions (EF0)Sets the condition for external fault detection (EF0).0: Always detected1: Detected only during operation0F6-03Stopping Method for ExternalFault from CommunicationOption BoardDetermines drive response for external fault input(EF0) detection during communication.0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only <2>1F6-07<3>NetRef/ComRef SelectionFunction0: Multi-step speed reference disabled1: Multi-step speed reference allowed 1F6-08<3>Reset Communication RelatedParametersDetermines if communication-related parameters F6- and F7- are set back to original defaultvalues when the drive is initialized using parameterA1-03.0: Do not reset F6- and F7- parameters1: Reset F6- and F7- parametersNote: Setting this parameter does not affectcommunication-related parameters.0