9 Option Drive Parameters44 YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation ManualF6-14 <6> bUS Error Auto Reset 0: Disabled1: Enabled 0F7-01 to F7-04 IP AddressSets static IP address of the SI-EP3/V option whenparameter F7-13=0.Note: Parameter F7-01 sets the most significant octet.192 168 1 20F7-05 to F7-08 Subnet Mask Sets static Subnet Mask of network connection.Note: Parameter F7-05 sets the most significant octet255 255 2550F7-09 to F7-12 Gateway Address Sets static Gateway address of network connection.Note: Parameter F7-09 sets the most significant octet. 192 168 1 1F7-13 Address Mode at StartupSelects how the option address is set.0: Static2: DCP2F7-14 Duplex Mode SelectionSelects duplex mode setting.0: Half duplex forced1: Auto-negotiate duplex mode and communicationspeed2: Full duplex forced3: Half (port 1)/Auto (port 2) <5>4: Half (port 1)/Full (port 2) <5>5: Auto (port 1)/Half (port 2) <5>6: Auto (port 1)/Full (port 2) <5>7: Full (port 1)/Half (port 2) <5>8: Full (port 1)/Auto (port 2) <5>1 <4>F7-15 Communication SpeedSelectionSets the communication speed.10: 10 Mbps100: 100 Mbps101: 10 (port 1)/100 Mbps (port 2) <5>102: 100 (port 1)/10 Mbps (port 2) <5>10F7-16 <6> Communication Loss TimeoutSets the timeout value for communication lossdetection in tenths of a second.A value of 0 disables the connection timeout.Example: An entered value of 100 represents 10.0seconds.0.0F7-23 to F7-27Option Firmware VersionVST800250Dynamic Output AssemblyParametersConfigurable outputs 1 to 5.If a value other than 0 is assigned to parameters F7-23to F7-27 and F7-33 to F7-37 by the drive, that valuewill take precedent over a value set by theconfiguration software. If the value in the drive is 0(default), the value from the configuration softwarewill be used. 0Option Firmware VersionVST800251Dynamic Output AssemblyParametersConfigurable outputs 1 to 5.If a value other than 0 is assigned in the configurationsoftware, those values will be used, otherwise, thevalues of the drive parameters set in parameters F7-23to F7-27 and F7-33 to F7-37 will be used.No. Name Description Default