11 TroubleshootingYASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 63Related ParametersTable 15 Parameters related to bUS Error Auto-Reset Functionality■ Option Fault Monitors U6-98 and U6-99The option can declare error/warning conditions via drive monitor parameters on the drivedigital operator as shown in Table 16.Table 16 Option Fault Monitor DescriptionsNo.(Addr. Hex)<2> If F6-01 is set to 3, then the drive will continue to operate when a bUS error is detected. Use caution and propersafety measures, when installing an emergency stop switch.<5> Available in drive software versions PRG:1024 and later when combined with option firmware versionVST800251 and later. Not available in drive software versions PRG:508.Name Description DefaultF6-01(03A2)Operation Selection afterCommunications ErrorDetermines drive response when a bUS error isdetected during communications with the option.0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only <2>4: Alarm (d1-04) <5>5: Alarm Ramp to Stop <5><6> Available in option firmware version VST800251 and later.1F6-14 <6>(03BB) bUS Error Auto Reset 0: Disabled1: Enabled 0F7-16 <6>(03F4) Communication Loss TimeoutSets the timeout value for communication lossdetection in tenths of a second.A value of 0 disables the connection timeout.Example: An entered value of 100 represents 10.0seconds.Note: A change to this parameter setting is noteffective until main power to the drive is cycled.0.0Fault Condition Fault Declared Status Value(U6-98/U6-99) DescriptionNo Fault n/a 0 No faults.Force Fault EF0 3 Network sent a message to force this node to the faultstate.Network LinkDown BUS ERROR 1300 No network link to option board.Network Failure BUS ERROR 1301 Connection with PLC Timeout.Default MACAddress None 1303 Factory default MAC Address programmed into theoption. Return for reprogramming.No IP Address None 1304 No IP Address has been programmed into the option.No Station Name None 1305 No Station Name has been programmed into the option.