Parameters 2139595 HW configuration Various hardware-related settings.95.01 Supply voltage Selects the supply voltage range. This parameter is used bythe drive to determine the nominal voltage of the supplynetwork. The parameter also affects the current ratings andthe DC voltage control functions (trip and brake chopperactivation limits) of the drive.WARNING! An incorrect setting may cause the motorto rush uncontrollably, or the overloading of the brakechopper or resistor.Not givenNot given No voltage defined. The drive will not start modulating beforeanother value is selected.0208…240 V 208…240 V 1380…415 V 380…415 V 2440…480 V 440…480 V 3500 V 500 V 4525…600 V 525…600 V 5660…690 V 660…690 V 695.02 Adaptive voltagelimitsEnables adaptive voltage limits.Adaptive voltage limits can be used if, for example, an IGBTsupply unit is used to raise the DC voltage level. If thecommunication between the inverter and IGBT supply unit isactive, the voltage limits are fixed to the DC voltage referencefrom the IGBT supply unit. Otherwise the limits are calculatedbased on the measured DC voltage at the end of the pre-charging sequence.DisableDisable Adaptive voltage limits disabled. 0Enable Adaptive voltage limits enabled. 195.04 Control boardsupplySpecifies how the control unit of the drive is powered. Internal 24VInternal 24V The drive control unit is powered from the drive power unit itis connected to. This is the default setting.0External 24V The drive control unit is powered from an external powersupply.1No. Name/Value Description Def/FbEq16