Application macros 69 Selection of constant speedsBy default, constant speeds 1…7 are selected using digital inputs DI4…DI6 asfollows: Default parameter settings for the Sequential control macroBelow is a listing of default parameter values that differ from those listed for theFactory macro in Additional parameter data (page 225).Parameter Sequential control macrodefaultNo. Name20.06 Ext2 commands In1 Start; In2 Dir20.08 Ext2 in1 DI620.09 Ext2 in2 DI522.12 Speed ref2 selection AI1 scaled22.14 Speed ref1/2 selection DI322.21 Constant speed function 01b (Bit 0 = Packed)22.22 Constant speed sel1 DI422.23 Constant speed sel2 DI522.24 Constant speed sel3 DI622.27 Constant speed 2 600.00 rpm22.28 Constant speed 3 900.00 rpm22.29 Constant speed 4 1200.00 rpm22.30 Constant speed 5 1500.00 rpm22.31 Constant speed 6 2400.00 rpm22.32 Constant speed 7 3000.00 rpm23.11 Ramp set selection DI331.11 Fault reset selection OffDI4 DI5 DI6 Constant speed active0 0 0 None (External speedreference used)1 0 0 Constant speed 10 1 0 Constant speed 21 1 0 Constant speed 30 0 1 Constant speed 41 0 1 Constant speed 50 1 1 Constant speed 61 1 1 Constant speed 7