Start-up 75Starting up ACS880 drives1. Power up the drive.2. Enable the communication between the adapter module andthe drive by setting parameter 50.01 FBA A enable to Enable.3. With parameter 50.02 FBA A comm loss func, select how thedrive reacts to a fieldbus communication break.Note: This function monitors both communication between thefieldbus master and adapter module and communicationbetween the adapter module and drive.4. With parameter 50.03 FBA A comm loss t out, define thetime between communication break detection and the selectedaction.5. Select application-specific values for parameters50.04…50.11. Examples of appropriate values are shown inthe tables below.6. Set the FCAN-01 configuration parameters in drive parametergroup 51.At minimum, set the required node address in parameter 51.02Node ID, the required bit rate in 51.03 Bit rate, select sourceof the PDO configuration in 51.04 Conf location and thecommunication profile in 51.05 Profile.7. If the group 51 is selected as the source for the PDOconfiguration, select the application specific configuration forthe PDOs with parameters 51.07…51.24.8. Define the process data transferred to and from the drive in theFCAN-01 configuration parameter groups 52 and 53.Note: If the PDO configuration is written from the PLC, theparameters 51.07…51.24 are not used and the parametergroups 52 and 53 display the process data selected in thePLC.