3-5Type 24Silent Burglary• Usually assigned to all sensors or contacts on exterior doors and windows wherebells and/or sirens are NOT desired.• Provides an instant alarm, with NO audible indication at any touchpad orexternal sounder, if the zone is faulted when the system is armed in the Away,Stay, or Instant, modes.• A report is sent to the central station.Type 25 *24-Hour Non-AlarmMonitor• For use with sensors designed to provide a trouble display (but no troublesounding) when an oil tank is low, or other similar application for criticalcondition monitoring where a non-alarm response is required.• When this zone type is faulted and remains faulted for the programmed timeduration (field *53), a special event message is sent to the central monitoringstation. The same holds true for restoration.Type 77Keyswitch• Assign to zone wired to a keyswitch.• Do not use devices assigned as input type “BR” with this zone type.Types 90-93ConfigurableThese zone types can be programmed for various custom responses. Configurableoptions include response to entry/exit delays, response opens and shorts, types ofalarm and trouble sounding, dial delay, type of display, and unique Contact IDreport codes.* The system can still be armed when these zone types are in a faulted condition.NOTE: All of the zone types described are available for the wireless portion of the system, if used.Mechanics of ProgrammingTo program the system from a touchpad:• You must use a 2-line Custom English display touchpad.• Both partitions must be disarmed.Data Field Programming ProceduresTask ProcedureEntering Program Mode A) Press both [∗] and [#] at the same time within 50 seconds after power is appliedto the control,ORB) After power-up, enter [Installer code (6-3-2-1)] + 8 0 0.(method “B” is disabled if you exit the program mode using ∗98)Go to a Data Field Press [∗] + [Field Number] (for example, ∗21).A display of “EE” or “Entry Error” means you have entered a nonexistent field.Simply re-enter [∗] plus a valid field number.Entering Data When the desired field number appears, simply enter the digits required. Thetouchpad beeps three times after the last digit is entered and automaticallydisplays the next data field in sequence.If entering less than the maximum digits available (e.g., phone number field),enter the desired digits, then press [∗] and the next data field number to beprogrammed to end the entry.Review a Data Field Press [#] + [Field Number].That field’s data is displayed, but no changes can be made.Deleting an Entry Press [∗] + [Field No.] + [∗] (applies only to phone number, account number, andpager character fields).