SiBE31-801_C Field SettingTest Operation 190 (Applied model: RTSYQ10~16P)k Disabling the inverter compressor from operatingSet No. 42 of setting mode 2 to "Disable-inverter compressor operation."k Disabling the STD compressor 1 (or STD compressor 2) from operatingSet No. 19 of setting mode 2 to "Disable-STD compressor 1 or 2 operation."k Disabling the STD compressor 2 from operating [RTSQ14 · 16P]Set No. 19 of setting mode 2 to "Disable-STD compressor 2 operation."• On the models RTSQ14P and 16P, if the INV compressor is set to "Operation prohibited",only one STD compressor will operate due to oil equalization.• On the models RTSQ14P and 16P, the STD compressor 1 cannot be set to "Operationprohibited" due to oil equalization.LED display (k: ON h: OFF l: Blink)(Step) H1P-----------H7P(1) Press the MODE button (BS1) for 5seconds or more. k h h h h h h(2) Press the SET button (BS2) 42 times. k k h k h k h(3) Press the RETURN button (BS3) once. k h h h h h l(4) Press the SET button (BS2) once. k h h h h l h(5) Press the RETURN button (BS3) twice. k h h h h h h(6) Press the MODE button (BS1) once. h h k h h h hLED display (k: ON h: OFF l: Blink)(Step) H1P-----------H7P(1) Press the MODE button (BS1) for 5seconds or more. k h h h h h h(2) Press the SET button (BS2) 19 times. k h k h h k k(3) Press the RETURN button (BS3) once. k h h h h h h(4) Press the SET button (BS2) once. k h h h h h l(5) Press the RETURN button (BS3) twice. k h h h h h h(6) Press the MODE button (BS1) once. h h k h h h hLED display (k: ON h: OFF l: Blink)(Step) H1P-----------H7P(1) Press the MODE button (BS1) for 5seconds or more. k h h h h h h(2) Press the SET button (BS2) 19 times. k h k h h k k(3) Press the RETURN button (BS3) once. k h h h h h h(4) Press the SET button (BS2) twice. k h h h h l h(5) Press the RETURN button (BS3) twice. k h h h h h h(6) Press the MODE button (BS1) once. h h k h h h h