SiBE31-801_C SpecificationsSpecifications 401-2 TECHNICAL SPECIFICATIONS FXMQ200MAVE FXMQ250MAVEPowerSupply Name VEPhase 1~Frequency Hz 50Voltage V 220-240Current Minimum circuit amps(MCA) A 8.1 9.0Maximum fuse amps(MFA) A 15 15Full load amps (FLA) A 6.5 7.2Voltagerange Minimum V -10%Maximum V +10%Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below orabove listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA : MCA = 1.25 × FLAMFA is smaller than or equal to 4 × FLANext lower standard fuse rating minimum 15ASelect wire size based on the MCAInstead of a fuse, use a circuit breaker