Field Setting SiBE31-801_C191 Test Operation (Applied model: RTSYQ20P)Make disable-operation setting by each outdoor unit.Make the following setting with the master unit. (Setting with the slave unit will be invalidated.)* Discriminate between the master unit and the slave unit according to LED displays shownbelow.k To prohibit the operation of master unit:Set the setting item No. 38 of "Setting mode 2" to "Master operation prohibited".k To prohibit the operation of slave unit:Set the setting item No. 39 of "Setting mode 2" to "Slave operation prohibited".• Systems with multi outdoor units cannot be set to "operation prohibited" by compressor.• If systems with multi outdoor units are set to "operation prohibited" as aforementioned,outdoor unit rotation will not be conducted. (Applied model: RTSYQ10~20P)Set the setting item No. 42 of "Setting mode 2" to "INV compressor operation prohibited".Make the following setting with the function unit.LED display (k: ON h: OFF l: Blink)H1P-----------H7P H8PMaster : h h k h h h h kSlave : h h h h h h h l (Factory setting)LED display (k: ON h: OFF l: Blink)(Step) H1P-----------H7P(1) Press and hold the MODE button (BS1)for a period of 5 sec. or more. k h h h h h h(2) Press the SET button (BS2) 38 times. k k h h k k h(3) Press the RETURN button (BS3) once. k h h h h h l (Factory setting)(4) Press the SET button (BS2) once. k h h h h l h(5) Press the RETURN button (BS3) twice. k h h h h h h(6) Press the MODE button (BS2) once. h h k h h h hLED display (k: ON h: OFF l: Blink)(Step) H1P-----------H7P(1) Press and hold the MODE button (BS1)for a period of 5 sec. or more. k h h h h h h(2) Press the SET button (BS2) 39 times. k k h h k k k(3) Press the RETURN button (BS3) once. k h h h h h l (Factory setting)(4) Press the SET button (BS2) once. k h h h h l h(5) Press the RETURN button (BS3) twice. k h h h h h h(6) Press the MODE button (BS2) once. h h k h h h hLED display (k: ON h: OFF l: Blink)(Step) H1P-----------H7P(1) Press and hold the MODE button (BS1)for a period of 5 sec. or more. k h h h h h h(2) Press the SET button (BS2) 42 times. k k h k h k h(3) Press the RETURN button (BS3) once. k h h h h h l (Factory setting)(4) Press the SET button (BS2) once. k h h h h l h(5) Press the RETURN button (BS3) twice. k h h h h h h(6) Press the MODE button (BS2) once. h h k h h h h