SiBE31-801_C SpecificationsSpecifications 48Concealed Floor Standing Unit1-2 ELECTRICAL SPECIFICATIONS FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVEPowerSupply Name VEPhase 1~Frequency Hz 50Voltage V 220-240Current Minimum circuit amps(MCA) A 0.3 0.3 0.6 0.6 0.6 0.6Maximum fuse amps(MFA) A 15 15 15 15 15 15Full load amps (FLA) A 0.2 0.2 0.5 0.5 0.5 0.5Voltagerange Minimum V -10%Maximum V +10%Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below orabove listed range limits.Maximum allowable voltage range variation between phases is 2%.MCA/MFA : MCA = 1.25 × FLAMFA is smaller than or equal to 4 × FLANext lower standard fuse rating minimum 15ASelect wire size based on the MCAInstead of a fuse, use a circuit breaker