Specifications SiBE31-801_C47 SpecificationsConcealed Floor Standing Unit1-1 TECHNICAL SPECIFICATIONS FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVECapacity Cooling kW 2.20 2.80 3.60 4.50 5.60 7.10Heating kW 2.50 3.20 4.00 5.00 6.30 8.00Power Input Cooling kW 0.049 0.049 0.090 0.090 0.110 0.110Heating kW 0.049 0.049 0.090 0.090 0.110 0.110Casing Material Galvanised steelDimensions Unit Height mm 610 610 610 610 610 610Width mm 930 930 1070 1070 1350 1350Depth mm 220 220 220 220 220 220Weight Unit kg 19 19 23 23 27 27HeatExchanger Dimensions Nr of Rows 3 3 3 3 3 3Fin Pitch mm 1.50 1.50 1.50 1.50 1.50 1.50Face Area m² 0.159 0.159 0.200 0.200 0.282 0.282Nr of Stages 14 14 14 14 14 14Fan Type Sirocco fanQuantity 1 1 1 1 1 1Airflow Rate Cooling High m³/min 7.00 7.00 8.00 11.00 14.00 16.00Low m³/min 6.00 6.00 6.00 8.50 11.00 12.00Fan Motor Quantity 1 1 1 1 1 1Model D14B20 D14B20 2D14B13 2D14B13 2D14B20 2D14B20Output(high) W 15 15 25 25 35 35Drive Direct driveRefrigerant Name R-410ACooling SoundPressure High dBA 35.0 35.0 35.0 38.0 39.0 40.0Low dBA 32.0 32.0 32.0 33.0 34.0 35.0Pipingconnections Liquid(OD) Type Flare connectionDiameter mm 6.35 6.35 6.35 6.35 6.35 9.52Gas Type Flare connectionDiameter mm 12.7 12.7 12.7 12.7 12.7 15.9Drain Diameter mm 21 21 21 21 21 21Heat Insulation Glass Fiber/Urethane FoamAir Filter Resin net with mold resistanceRefrigerant control Electronic expansion valveTemperature control Microprocessor thermostat for cooling and heatingSafety devices PCB fuseFan motor thermal protectorStandardAccessories Standard Accessories Installation and operation manualInsulation for fittingDrain hoseClampsScrewsWasherLevel adjustment screwNotes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,equivalent refrigerant piping : 7.5m (horizontal)Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,equivalent refrigerant piping : 7.5m (horizontal)Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.Sound pressure levels are measured at 220V