SiBE31-801_C Troubleshooting by Remote ControllerTroubleshooting 2103.5 Inspection ModeOperating the INSPECTION/TEST button on the remote controller will make it possible tocheck the malfunction codes, indoor unit model codes, and outdoor unit model codes while ininspection mode.Normal display (No display)Inspection/testoperation Push the button.Malfunction code blinks when a malfunction occurs.UnitMalfunction codeInspection0L 0UnitMalfunction codeInspection0L 0Inspection modeInspection/testoperation Push the button.0 7 1F C JIndoor unit model code displayPush the button.Inspection/testoperation– – –A A 1Outdoor unit model code displayPush the button.Inspection/testoperationTest operationTest operation modePush the button.Inspection/testoperationCapacity codeIndoor unit system codeIndoor unit type codeProgression code0 7 1...F...C...J...Example of capacity code displayExample model DisplayFXCQ25 028FXFQ63 071Indoor unit system codeIndoor unit type codeDisplay Product classification System classification1 VRV system (VAV indoor unit)2 VRV system Outdoor air processing unitF VRV system Standard indoor unitH VRV system New ceiling suspended cassetteDisplay Type ModelA Wall mounted FXAQC 2-way blow FXCQE Corner FXKQF Roundflow FXFQH Ceiling suspended FXHQJ Concealed ceiling FXSQP Floor standing FXLQU Concealed ceiling FXMQL Concealed floor standing type FXNQ6 600×600 4-way blow FXZQ3 Slim concealed ceiling FXDQOutdoor model codeDisplay Type ModelA A 1 VRV System Inverter K Series RSXYPA A 3 R-407C VRV PLUS Series RXYPA 9 2 VRV Heat Recovery Series RSEYPA A 5 High COP type R-407C L Series RSXYP-LA A A VRV II RXYQ-MA A C VRV II M/C RXYQ-MAA A E VRV III Heat Pump Series RXYQ-PCooling Only Series RXQ-PA 9 E VRV III Heat Recovery Series REYQ-PA 5 E VRV III-C Heat Pump Series RTSYQ-P